BGE Loss Factors
Losses naturally occur as a result
of transporting electricity from power plants to the points of
utilization. These losses vary with the location and magnitude of
the load, as well as with voltage level, equipment type, wire size,
configuration and the location of generation. There are also
'no-load' losses associated with energizing transformers.
BGE's loss determination method
utilizes a combination of widely accepted network analysis techniques
and approximated values to calculate losses. The method is composed of
three basic steps as follows.
1. Losses associated with the bulk
transmission and sub-transmission systems are determined using Power
Technologies, Inc.'s PSS/ET package, based upon historical load and
generation patterns. The losses, which vary with system loading
conditions, as well as transformer no-load losses, are allocated to
customers connected at the 230kV, 115kV, 34.5kV and 13.8/4kV portions
of the system, based on the total load at that voltage. This
apportionment technique is similar to PJM's approach to allocating
500kV losses.
2. Distribution line losses are
approximated using PTI's PSS/U package. These losses are allocated
between primary and secondary connected customers using the system
average customer load connected for the respective customer
classifications.
3. Losses associated with energizing
distribution transformers, as well as losses resulting from
distribution transformer loading, are approximated using transformer
manufacturers' data and average transformer loading information for
the system. Losses associated with loads on secondary and service
connections are approximated using data based upon system averages.
Losses associated with through flow
are compensated through the PJM guidelines and procedures.
Resulting loss factors are estimated
as follows. (These loss factors do not include losses associated
with Unaccounted For Energy)
|
Voltage Class |
Loss Factor |
|
Primary Voltage |
|
|
230 kV |
0.878% |
|
115 kV |
1.622% |
|
34 kV |
2.473% |
|
13 and 4 kV |
3.660% |
|
Secondary Voltage |
6.665% |
|